Integration of Two Serial Interfaces Into a CANopen Network
- Configuration of physical serial interfaces via piggybacks
-
2x RS-232 or optional 1x RS-232 and 1x RS-485 serial interfaces
-
ARM7 Microcontroller
User Friendly CANopen Module with Solid InRailBus Technology
-
InRailBus technology combines high ease of use and proven reliability
-
CANopen profiles acc. to CiA® specification CiA 301 and CiA DSP 302
Configuration of Serial Interfaces
-
Serial communication parameters can be configured in a flexible range
Serial Interface
Two serial interfaces can be connect to a CAN net. In the standard version the physical layers are realized as two RS-232 interfaces.
Instead of the driver for RS-232 interfaces, the module can be equipped with piggybacks for RS-422, RS-485 or TTY active/passive interfaces.
CAN Interface
The CAN interface is designed according to ISO 11898-2 high-speed layer with electrical isolation and supports bit rates up to 1 Mbit/s. The CANopen-node number and the CAN bit rate can be easily set via coding switches.
InRailBus for easy wiring
The power supply and the CAN bus signals can be supplied via the InRailBus connector (TBUS connector) integrated in the mounting rail. In this way, a minimum of cabling of the individual modules is achieved. All esd CBX modules are compatible with each other and can be plugged onto the bus as required. It is also possible to disconnect individual modules from the InRailBus without interrupting the bus signals or the power supply.
Do you have special requirements regarding the product?
We are happy to provide you with a customer-specific option or adjustment to our products when purchasing appropiate quantities. Please contact our sales team for detailed information.
With the help of the button "Add to watchlist" you can save articles on your watchlist.
Afterwards, you can request your saved watch list as a quotation via a contact form.
Hardware
CANopen module for 2 serial RS232 interfaces. Configuration and protocol according CANopen DS301, CAN Interface according to ISO 11898, galvanic isolation via optocoupler, supports In-Rail-Bus
- CiA 301 compliant
- CiA 401 profile
- galvanically isolated
- CAN
- CANopen Device
- Serial Interface
- CAN-Layer 2
- CANopen