CAN-CBM-DP

PROFIBUS-DP®/CAN Gateway

Features

  • Fast and reliable linking PROFIBUS-DP and CAN

  • Application examples: SIMATIC-S7 to CAN layer 2 or CANopen®

  • DP-slave with up to 300 bytes data (partitioning from up to 240 bytes input and 60 bytes output to 240 bytes output and 60 bytes input)

  • CAN master: CAN layer 2, no limitation on CANopen PDO's and SDO's

  • No limitation on the number of CAN participants by the module

There is an alternative product,

Please have a look at: CAN-DP/2

Linking DP and CAN

The module CAN-CBM-DP can link any Profibus-DP master to a CAN network. The DP/CAN gateway operates as a slave-I/O component with a total of maximum 300 bytes data (partitioning from up to 240 bytes input and 60 bytes output to 240 bytes output and 60 bytes input data) on the DP-bus.

Applications

With the CAN gateway you can couple CAN modules with CANopen or layer-2 implementation to e.g. a SIMATIC-S7. The number of CAN participants is not limited by the module.

Physical Interfaces

The ISO 11898-compatible CAN interface allows a maximum data-transfer rate of 1 Mbit/s. The Profibus-DP-Slave interface automatically recognizes all usual bit rates up to 12 Mbit/s. The DP as well as the CAN interface are electrically isolated by optocouplers and DC/DC converters.

Serial Interface

The module has a serial interface (default: RS-232) for service and configuration. It is connected by a DSUB9 connector.

Configuration and CAN protocols

For the I/O data mapping of the DP slave a configuration software for Windows95/98 or Windows NT is available. CANopen is supported as Layer-7 protocol on the CAN layer.

PNO Logo

esd electronics has been a member of the PROFIBUS user organisation e.V. (PNO) for many years.

Do you have special requirements regarding the product?

We are happy to provide you with a customer-specific option or adjustment to our products when purchasing appropiate quantities. Please contact our sales team for detailed information.


Software Downloads

More questions? We are pleased to help you


Order items and accessories

With the help of the button "Add to watchlist" you can save articles on your watchlist.
Afterwards, you can request your saved watch list as a quotation via a contact form.

Hardware

Number: C.2844.03

CANbloc-Mini DIN-rail module Profibus-DP-Slave / CAN-layer 2 Gateway, CAN-physical Layer according to ISO11898, electrically isolated data transfer rates up to 1 MBit/s, DP-Physical Layer: RS-485, electrically isolated; Manual and GSD file on CD-ROM

Features:
  • galvanically isolated
Interfaces:
  • CAN
  • Profibus
  • Serial Interface
Form factor: Railmount  
Protocols:
  • CAN-Layer 2
  • Profibus
HS Code: 85176200
Number: C.2844.05

CANbloc-Mini DIN-rail module Profibus-DP-Slave / CAN-layer 2 Gateway, for CAN 2.0B, 29 Bit support, CAN-physical Layer according to ISO11898, electrically isolated, data transfer rates up to 1 MBit/s, DP-Physical Layer: RS-485, electrically isolated; Manual and GSD file on CD-ROM; additionally the RS-232 can be used for service, development or configuration purposes

Features:
  • galvanically isolated
Interfaces:
  • CAN
  • Profibus
  • Serial Interface
Form factor: Railmount  
Protocols:
  • CAN-Layer 2
  • Profibus
HS Code: 85176200

Hardware-Accessories

Number: C.1323.03

CAN cable assembly, 0.3 m length, 1 x DSUB-9 plug and 3 wire end sleeves, performance level 3, metallised plastic housing

HS Code: 85444290
Number: C.1323.04

manufactured CAN cable, length 0.3 m, 1 x DSUB-9 socket and 3 wire end sleeves, performance level 3, metallised plastic housing

HS Code: 85444290