esd offers a wide range of compact stand-alone I/O modules for CANopen and EtherCAT. The modules of the CAN-CBX series offer the possibility of easy mounting in the DIN rail due to the InRailBus. All CANopen modules operate according to CANopen profiles in compliance with the CiA® specification CiA 301.
With the help of the button "Add to watchlist" you can save articles on your watchlist.
Afterwards, you can request your saved watch list as a quotation via a contact form.
Selected filters
Protocols
Interfaces
Features
CAN-CBX-Pt100
C.3032.02CANopen module with 4 independent channels with 24-bit Sigma-Delta ADC for high-precision RTD (e.g. Pt100 or Ni100) and resistance measurements. Measurements in two- or four-wire technology with selectable sampling rates of up to 1000 PLC. CANopen according to CiA 301 and CiA 404 Device Profile Measuring Devices. Connectors for wire end ferrules included in the scope of delivery.
CAN-CBX-THERMO
C.3034.02CANopen module with 4 independent, galvanically isolated channels with 24-bit Sigma-Delta ADC for high-precision temperature and voltage measurements. Suitable for thermocouples of types J, K, B, E, N, R, S or T as well as integrated cold junction compensation. CANopen according to CiA 301 and CiA 404 Device Profile Measuring Devices. Connector plug for wire end ferrules included in the scope of delivery.