CAN-CBX-AI814

CANopen® Module with 8 Analog Inputs

8 A/D-Converter Inputs

  • Resolution: 14 bit

  • Input voltage range: ±10.24 V

  • Sample rate: up to 100 μs / 8 channels simultaneously

  • CANopen profiles according to CiA® specification CiA 301 and CiA 401

Compact-I/O-Module

The CAN-CBX module series with InRailBus offers industry-compatible CAN bus input/output modules in combination with user-friendly 'wiring' of CAN bus and supply voltage.

Approved Reliability and Ease of Use

  • Electrical isolation of analog inputs
  • InRailBus technology combines high ease of use and proven reliability

  • DIN-EN carrier rail mounting (TS 35)

Firmware adaptable to Customer Requirements via CANopen

Analog Inputs

The CAN-CBX-AI814 module is equipped with an A/D-converter that offers eight analog input channels with a resolution of 14 bit

Compact I/O modules with DIN rail mounting

The CAN-CBX series is equipped with the InRailBus used by esd and offers industry-compatible CAN bus input/output modules in combination with user-friendly "wiring" of CAN bus and supply voltage.

CAN Interface and LED Display

The CAN interface is designed according to ISO11898-2 high-speed layer with electrical isolation and supports bit rates up to 1 Mbit/s. The CANopen-node number and the CAN bit rate can be easily set via coding switches.
Four LEDs indicate the module and CANopen node status.

InRailBus for easy wiring

The power supply and the CAN bus signals can be supplied via the InRailBus connector (TBUS connector) integrated in the mounting rail. In this way, a minimum of cabling of the individual modules is achieved. All esd CBX modules are compatible with each other and can be plugged onto the bus as required. It is also possible to disconnect individual modules from the InRailBus without interrupting the bus signals or the power supply.

Software Support

The CAN-CBX-AI814 comes with CANopen firmware according to CiA 301 and and with a CANopen-I/O profile according to CiA 401.

CANopen Logo

esd electronics develops its products according to CiA® specifications.

Do you have special requirements regarding the product?

We are happy to provide you with a customer-specific option or adjustment to our products when purchasing appropiate quantities. Please contact our sales team for detailed information.


Documentation

Software Downloads

More questions? We are pleased to help you


Order items and accessories

With the help of the button "Add to watchlist" you can save articles on your watchlist.
Afterwards, you can request your saved watch list as a quotation via a contact form.

Hardware

Number: C.3020.02

CANopen module with 8 analog single-ended inputs for the ±10V voltage range. Inputs with 14-bit resolution, data rates up to 1kHz and galvanic isolation. CANopen according to CiA 301 and CiA 401 Device Profile for Generic I/O Modules. Connectors for wire end ferrules included in the scope of delivery.

Features:
  • CiA 301 compliant
  • CiA 401 profile
  • galvanically isolated
Interfaces:
  • CAN
  • CANopen Device
Form factor: Railmount  
I/O:
  • Analog Input
Protocols:
  • CAN-Layer 2
  • CANopen
HS Code: 85176200

Hardware-Accessories

Number: C.1323.03

CAN cable assembly, 0.3 m length, 1 x DSUB-9 plug and 3 wire end sleeves, performance level 3, metallised plastic housing

HS Code: 85444290
Number: C.1323.04

manufactured CAN cable, length 0.3 m, 1 x DSUB-9 socket and 3 wire end sleeves, performance level 3, metallised plastic housing

HS Code: 85444290
Number: C.3000.01

In-Rail-Bus connector

Form factor: Railmount  
HS Code: 85177900
Number: C.3000.02

to connect power supply (24V) and CAN at CBX-In-Rail-Bus. socket type

Form factor: Railmount  
HS Code: 85366990
Number: C.3000.03

to connect power supply (24V) and CAN at CBX-In-Rail-Bus. plug type

HS Code: 85366990